Логотип exploitDog
Консоль
Логотип exploitDog

exploitDog

nvd логотип

CVE-2022-30313

Опубликовано: 28 июл. 2022
Источник: nvd
CVSS3: 7.5
EPSS Низкий

Описание

Honeywell Experion PKS Safety Manager through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0051, there is a Honeywell Experion PKS Safety Manager multiple proprietary protocols with unauthenticated functionality issue. The affected components are characterized as: Honeywell Experion TCP (51000/TCP), Safety Builder (51010/TCP). The potential impact is: Manipulate controller state, Manipulate controller configuration, Manipulate controller logic, Manipulate controller files, Manipulate IO. The Honeywell Experion PKS Distributed Control System (DCS) Safety Manager utilizes several proprietary protocols for a wide variety of functionality, including process data acquisition, controller steering and configuration management. These protocols include: Experion TCP (51000/TCP) and Safety Builder (51010/TCP). None of these protocols have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a su

Ссылки

Уязвимые конфигурации

Конфигурация 1

Одновременно

cpe:2.3:o:honeywell:safety_manager_firmware:-:*:*:*:*:*:*:*
cpe:2.3:h:honeywell:safety_manager:-:*:*:*:*:*:*:*

EPSS

Процентиль: 44%
0.00212
Низкий

7.5 High

CVSS3

Дефекты

CWE-306

Связанные уязвимости

CVSS3: 7.5
github
больше 3 лет назад

Honeywell Experion PKS Safety Manager through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0051, there is a Honeywell Experion PKS Safety Manager multiple proprietary protocols with unauthenticated functionality issue. The affected components are characterized as: Honeywell Experion TCP (51000/TCP), Safety Builder (51010/TCP). The potential impact is: Manipulate controller state, Manipulate controller configuration, Manipulate controller logic, Manipulate controller files, Manipulate IO. The Honeywell Experion PKS Distributed Control System (DCS) Safety Manager utilizes several proprietary protocols for a wide variety of functionality, including process data acquisition, controller steering and configuration management. These protocols include: Experion TCP (51000/TCP) and Safety Builder (51010/TCP). None of these protocols have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a...

EPSS

Процентиль: 44%
0.00212
Низкий

7.5 High

CVSS3

Дефекты

CWE-306