Логотип exploitDog
Консоль
Логотип exploitDog

exploitDog

nvd логотип

CVE-2022-30316

Опубликовано: 28 июл. 2022
Источник: nvd
CVSS3: 6.8
EPSS Низкий

Описание

Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over-ethernet link with the DCOM-232/485 interface. Firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. Firmware images are unsigned. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize hardcoded cred

Ссылки

Уязвимые конфигурации

Конфигурация 1

Одновременно

cpe:2.3:o:honeywell:safety_manager_firmware:-:*:*:*:*:*:*:*
cpe:2.3:h:honeywell:safety_manager:-:*:*:*:*:*:*:*

EPSS

Процентиль: 32%
0.0012
Низкий

6.8 Medium

CVSS3

Дефекты

CWE-354

Связанные уязвимости

CVSS3: 6.8
github
около 3 лет назад

Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over-ethernet link with the DCOM-232/485 interface. Firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. Firmware images are unsigned. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize hardcoded c...

CVSS3: 9.8
fstec
около 3 лет назад

Уязвимость встроенных образов контроллеров противоаварийной защиты Safety Manager и микропрограммного обеспечения программируемых логических контроллеров Honeywell Experion PKS, позволяющая нарушителю оказать воздействие на конфиденциальность, целостность, доступность защищаемой информации

EPSS

Процентиль: 32%
0.0012
Низкий

6.8 Medium

CVSS3

Дефекты

CWE-354