Описание
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
Ссылки
- ExploitThird Party Advisory
- ExploitThird Party Advisory
Уязвимые конфигурации
Одновременно
Одновременно
Одновременно
Одновременно
Одновременно
Одновременно
Одновременно
EPSS
9.8 Critical
CVSS3
7.5 High
CVSS3
5 Medium
CVSS2
Дефекты
Связанные уязвимости
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
EPSS
9.8 Critical
CVSS3
7.5 High
CVSS3
5 Medium
CVSS2