Логотип exploitDog
bind:CVE-2022-30315
Консоль
Логотип exploitDog

exploitDog

bind:CVE-2022-30315

Количество 2

Количество 2

nvd логотип

CVE-2022-30315

больше 3 лет назад

Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion PKS Safety Manager insufficient logic security controls issue. The affected components are characterized as: Honeywell FSC runtime (FSC-CPU, QPP), Honeywell Safety Builder. The potential impact is: Remote Code Execution, Denial of Service. The Honeywell Experion PKS Safety Manager family of safety controllers utilize the unauthenticated Safety Builder protocol (FSCT-2022-0051) for engineering purposes, including downloading projects and control logic to the controller. Control logic is downloaded to the controller on a block-by-block basis. The logic that is downloaded consists of FLD code compiled to native machine code for the CPU module (which applies to both the Safety Manager and FSC families). Since this logic does not seem to be cryptographically authenticated, it allows an attacker capable of trigger

CVSS3: 9.8
EPSS: Низкий
github логотип

GHSA-rqm7-h39v-q6cr

больше 3 лет назад

Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion PKS Safety Manager insufficient logic security controls issue. The affected components are characterized as: Honeywell FSC runtime (FSC-CPU, QPP), Honeywell Safety Builder. The potential impact is: Remote Code Execution, Denial of Service. The Honeywell Experion PKS Safety Manager family of safety controllers utilize the unauthenticated Safety Builder protocol (FSCT-2022-0051) for engineering purposes, including downloading projects and control logic to the controller. Control logic is downloaded to the controller on a block-by-block basis. The logic that is downloaded consists of FLD code compiled to native machine code for the CPU module (which applies to both the Safety Manager and FSC families). Since this logic does not seem to be cryptographically authenticated, it allows an attacker capable of trig...

CVSS3: 9.8
EPSS: Низкий

Уязвимостей на страницу

Уязвимость
CVSS
EPSS
Опубликовано
nvd логотип
CVE-2022-30315

Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion PKS Safety Manager insufficient logic security controls issue. The affected components are characterized as: Honeywell FSC runtime (FSC-CPU, QPP), Honeywell Safety Builder. The potential impact is: Remote Code Execution, Denial of Service. The Honeywell Experion PKS Safety Manager family of safety controllers utilize the unauthenticated Safety Builder protocol (FSCT-2022-0051) for engineering purposes, including downloading projects and control logic to the controller. Control logic is downloaded to the controller on a block-by-block basis. The logic that is downloaded consists of FLD code compiled to native machine code for the CPU module (which applies to both the Safety Manager and FSC families). Since this logic does not seem to be cryptographically authenticated, it allows an attacker capable of trigger

CVSS3: 9.8
1%
Низкий
больше 3 лет назад
github логотип
GHSA-rqm7-h39v-q6cr

Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion PKS Safety Manager insufficient logic security controls issue. The affected components are characterized as: Honeywell FSC runtime (FSC-CPU, QPP), Honeywell Safety Builder. The potential impact is: Remote Code Execution, Denial of Service. The Honeywell Experion PKS Safety Manager family of safety controllers utilize the unauthenticated Safety Builder protocol (FSCT-2022-0051) for engineering purposes, including downloading projects and control logic to the controller. Control logic is downloaded to the controller on a block-by-block basis. The logic that is downloaded consists of FLD code compiled to native machine code for the CPU module (which applies to both the Safety Manager and FSC families). Since this logic does not seem to be cryptographically authenticated, it allows an attacker capable of trig...

CVSS3: 9.8
1%
Низкий
больше 3 лет назад

Уязвимостей на страницу